SUSQUEHANNA RIVER GAUGE

SHAMOKIN CREEK GAUGE

SPRING RUN GAUGE

WATER LEVEL OPERATING ELEVATIONS

  • 12 FEET SUSQUEHANNA

    Activate Reagan Street Pumping Station and close gravity gates

  • 14.4 FEET SUSQUEHANNA

    Activate Church Street Pumping Station and close gravity gates

  • 16 FEET SUSQUEHANNA

    Check Shamokin Creek drainage structures for debris and/or obstructions

  • 17 FEET SUSQUEHANNA

    Check Drainage Structure #6 (Lower Susquehanna Section) for debris and/or obstructions

  • 18 FEET SUSQUEHANNA

    Check Shamokin Creek Drainage Structure #2 for infiltration. Activate Spring Run pumping station pump #3 and close gravity gates

  • 19 FEET SUSQUEHANNA

    Activate Hopper Alley Pumping Station and close gravity gates. Monitor all pump stations every 4-hours in the event of rain or high runoff. Activate Underpass Pumping Station and close gravity gates. Pre-inspect all closure structures. Make arrangements for the possibility of hauling additional sand

  • 20 FEET SUSQUEHANNA

    Check Shamokin Creek drainage structure #3 for infiltration

  • 21 FEET SUSQUEHANNA

    Begin monitoring all Shamokin Creek drainage structures for infiltration

  • 22 FEET SUSQUEHANNA

    Entrance to sand supply plant begins inundation

  • 25 FEET SUSQUEHANNA

    Possible closure installation situation

    Contact PennDOT of possible closure - Closure Structure #3 (East Market St.)

  • 26 FEET SUSQUEHANNA

    Place personnel at the Flood Control Operations Center 24 hours a day

  • 27 FEET SUSQUEHANNA

    Begin 24-hour monitoring of levee - Initiate Sectional Plan

    Contact River Forecast Center/Weather Service for Updates

    Contact volunteers and put them on stand-by

    Contact Authority managers and put all personnel on stand-by

    Contact City crew and put them on stand-by

    Contact electricians and put them on stand-by

  • 28 FEET SUSQUEHANNA

    Place 2 operators at Front St. pumping stations

    Restrict access on grassy areas of system

    Contact media for assistance in filling sandbags and miscellaneous work detail

    Contact CP Rail of possible closure - Closure Structure #1 (VFW)

  • 29 FEET SUSQUEHANNA

    Install Closure Structure #1 (VFW), notify CP Rail, local officials and media of closure

  • 30 FEET SUSQUEHANNA

    Begin 24-hour monitoring of the wall - Initiate Sectional Plan

  • 31 FEET SUSQUEHANNA

    Contact Norfolk Southern of possible closures

  • 32 FEET SUSQUEHANNA

    Install Closure Structure #6

    - Norfolk Southern tracks - Weis Markets

    Notify Norfolk Southern, local officials and media

    Install Closure Structure #7

    - Norfolk Southern tracks - near Underpass Pump Station

     

  • 35 FEET SUSQUEHANNA

    Limit of Protection

  • 3.3 FEET SHAMOKIN

    Check Shamokin Creek drainage structures for debris and/or obstructions

  • 4.1 FEET SHAMOKIN

    Check Shamokin Creek Drainage Structure #2 for infiltration. Activate Spring Run pumping station pump #3 and close gravity gates

  • 9.7 FEET SHAMOKIN

    Begin monitoring all Shamokin Creek drainage structures for infiltration

  • 14 FEET SHAMOKIN

    Possible closure installation situation

    Contact PennDOT of possible closure - Closure Structure #3 (East Market St.)

  • 15 FEET SHAMOKIN

    Begin 24-hour monitoring of levee - Initiate Sectional Plan

    Contact River Forecast Center/Weather Service for Updates

    Contact volunteers and put them on stand-by

    Contact Authority managers and put all personnel on stand-by

    Contact City crew and put them on stand-by

    Contact electricians and put them on stand-by

  • 16 FEET SHAMOKIN

    Install Closure Structure #1 (VFW), notify CP Rail, local officials and media of closure

  • 17 FEET SHAMOKIN

    Install Closure Structure #3 (East Market St.)

  • 19 FEET SHAMOKIN

    Install Closure Structure #4 (Zimmerman's)

    Install Closure Structure #5

    - South 10th Street Bridge

    30 feet Susquehanna

     

  • 428.5 FEET SPRING RUN

    Check Shamokin Creek Drainage Structure #2 for infiltration. Activate Spring Run pumping station pump #3 and close gravity gates

  • 429.5 FEET SPRING RUN

    Activate Spring Run pumping station flood pumps

Flood Operations Center

826 Hillside Road

Sunbury, Pennsylvania 17801

All contents © 2015 Sunbury Municipal Authority   |   site design: BLH Media